M-7015, 6 Channels Input Module for RTD Type Pt-100, Ni-120, Cu-100, Cu-1000 with Isolation, Individual Channel Configuration, Modbus
| Features |
- Input Type : Supports 2/3 wire RTD
- Input channel : 6
- RTD Range : Pt100,Pt1000, Ni120, Cu100, Cu1000
- Resolution : 16-bit
- Accuracy : +/-0.05%
- Sampling Rate : 12 samples/second (Total)
- -3dB BandWidth : 5.24Hz
- Common Mode Rejection : Typical 86dB
- Voltage Input Impedance : >1M Ohms
- Individual Channel Configurable
- Open Wire Detection
- Isolation Voltage : 3000Vdc
- 4KV ESD Protection:Yes, Contact for each terminal.
|
Technical parameters
| Construction | | Construction | Module with Serial Interface,DIN Rail Mounting,Plastic Case | | Interface | | Interface | Type | RS-485 | | Data Transfer Rate | 1200,2400,4800,9600,19200,38400,57600,115200 Bit/sec | | Max Communication Distance | 1200 m | | Communication Protocol | Protocol Compatible with ADAM-4000,Modbus RTU | | Max Modules Number in Network | 2048 | | Analog Input | | Analog Input Channels | Total | 6 | | Differential | 6 | | Input Sensor | RTD | Ni 120,Pt 100 a=0.003916,Pt 100 a=0.00385,Cu 1000 a=0.00421,Pt 1000 a=0.00385,Cu 100 a=0.00421 (2 or 3 wire connection, Separate Channel Configuration) | | Input Impedance | Voltage Inputs | 1 MOhm | | Input | Max Input Overvoltage | 35 V | | Bandwidth | 5.24 Hz | | AD Converter | Resolution | 16 bit | | Speed | 12 Samples/sec | | Conversion Type | Sigma-Delta ADC | | Trigger Mode | Pacer | | Isolation | 3000 V | | Accuracy | -0.05...0.05 % | | CMRR | 86 dB | | Processor | | On Board CPU | 8051 Compatible | | Watchdog Timer | | Watchdog Timer | Yes | | Cables & Connectors | | Connectors | Screw Terminal | | Power | | Power Requirements | +10...+30V | | Power Consumption | 1.1 W | | MTBF | | MTBF | 80000 h | | Operation | | Operation | Temperature | -20...+75 °C | | Dimensions and Weight | | Dimensions | Length | 122 mm | | Depth | 72 mm | | Height | 25 mm | | Certifications | | GOST Certificate (Russia) | ROSS TW.AIO64.B03757 |
|